Holy shit I hope these weren't on line too... The only live electrical I came across was in the first floor of Jensen hall.
|
|
Posted by THWN2 |
4/11/2006 11:23 PM | remove |
Iwounder if they had PCBs
|
|
Posted by vwtype3guy |
4/15/2006 9:19 PM | remove |
Holy shit is right! These were happily humming away as well.
|
|
Posted by THWN2 |
12/24/2018 1:46 AM | remove |
This is a 3 phase bank made up of three 100 kva 1 phase transformers which is 300 kva 3 phase most likely 120/208 volt on the secondary the amperage those transformers put out at 208 volts is 832 amps .The switch gear on the other side is most likely 1,200 amps with three 500 mcm cables per leg if that has four 500 mcm cables per leg it would be 1,600 amp gear. Utilities are known to under size transformers they size to your max load not to what you main overcurrent device is.
|